<div dir="ltr">You might also crank up the priority on your resilver, particularly if it is getting tripped all of the time:<div><a href="http://broken.net/uncategorized/zfs-performance-tuning-for-scrubs-and-resilvers/">http://broken.net/uncategorized/zfs-performance-tuning-for-scrubs-and-resilvers/</a><br></div><div> -nld</div></div><div class="gmail_extra"><br><div class="gmail_quote">On Tue, Jun 9, 2015 at 1:31 PM, Dave Pooser <span dir="ltr"><<a href="mailto:dave-oo@pooserville.com" target="_blank">dave-oo@pooserville.com</a>></span> wrote:<br><blockquote class="gmail_quote" style="margin:0 0 0 .8ex;border-left:1px #ccc solid;padding-left:1ex"><div class="HOEnZb"><div class="h5">>This is probably a silly question, but I¹ve honestly never tried this and<br>
>don¹t have a test machine handy at the moment ­ can a pool be safely<br>
>exported and re-imported later if it is currently resilvering?<br>
><br>
>In the way of a bit of background, I have a pool made up with thirty or<br>
>so 4TB Seagate disks with a firmware issue that results in their max temp<br>
>being set at 40C as opposed to 60C. This particular pool is<br>
> in an office building in Texas, in an air-conditioned server room. The<br>
>condenser for this unit is in the building¹s plenum and when the building<br>
>a/c goes off over weekends in the summer my server room a/c struggles and<br>
>temps run up to about 85F or so. This<br>
> is causing my pool to drop random disks lately (fmadm reports high temp<br>
>and they get marked as removed from the pool), and I¹ve only just<br>
>narrowed it down to this firmware issue. Seagate firmware update utility<br>
>is apparently Windows only, so the disks must<br>
> come out for the firmware update, but the pool is resilvering several<br>
>disks with days remaining, hence my original query.<br>
<br>
</div></div>Not an answer to your question, but the approach I'd take is renting a<br>
portable 110V or 220V A/C unit from somebody like <a href="http://spot-coolers.com" target="_blank">spot-coolers.com</a> to get<br>
you through the resilver, then apply the firmware update. (And then I'd<br>
start trying to convince management that it's worth adding a unit<br>
permanently -- our Office Pro 24 24000BTU/hr cost us under $4k back in<br>
2011.)<br>
<span class="HOEnZb"><font color="#888888">--<br>
Dave Pooser<br>
Cat-Herder-in-Chief, Pooserville.com<br>
<br>
<br>
_______________________________________________<br>
OmniOS-discuss mailing list<br>
<a href="mailto:OmniOS-discuss@lists.omniti.com">OmniOS-discuss@lists.omniti.com</a><br>
<a href="http://lists.omniti.com/mailman/listinfo/omnios-discuss" target="_blank">http://lists.omniti.com/mailman/listinfo/omnios-discuss</a><br>
</font></span></blockquote></div><br></div>